Electromagnetic Flowmeters — Magmeters for Conductive Liquids
An electromagnetic flowmeter (magmeter) measures the flow of electrically conductive liquids with no moving parts and no pressure drop. Pioneer supplies inline magmeters from DN 10 to DN 2000 with accuracy of ±0.5% of measured value (±0.2% on request), for velocities of 0.2 to 12 m/s in either direction.
- Measuring range: 0.2 to 12 m/s, bidirectional
- Nominal size: DN 10 to DN 2000
- Accuracy: ±0.5% of measured value (±0.2% on request)

Overview
What it does and where it fits.
A magmeter works on Faraday's law. Coils around the flow tube create a magnetic field, and a conductive liquid moving through it generates a voltage proportional to its velocity, which two electrodes pick up. Because the field strength and electrode spacing are fixed, the signal depends only on velocity, so viscosity, density and temperature changes do not affect the reading.
The liquid must conduct electricity: the installation manual calls for more than 10 µS/cm. That covers potable water, raw water, sewage, cooling water, most acids, alkalis and slurries, but not oils, hydrocarbons, solvents, demineralised water or gases. For those, use a vortex, turbine, ultrasonic or mass flowmeter.
Each meter is configured to order: integral or remote transmitter, liner, electrode, end connection and pressure rating. The tables below list the ordering options, the minimum and maximum flow for every size at 0.2 and 12 m/s, and the installation rules a site team must follow.
Types
- Integral typeTransmitter mounted on the flow tube, for accessible locations where one compact unit is preferred.
- Remote typeFlow tube with junction box and a separate wall- or pipe-mounted transmitter, connected by a 10 m standard cable; allows an IP68 flow tube for pits and flood-prone chambers.
- Flanged, wafer and sanitary endsFlanges to ANSI 150, DIN PN or BS 10 Table D/E, wafer pattern, or SMS and tri-clamp ends for food and pharmaceutical lines.
- Solar or battery poweredListed ordering options for remote water lines without a mains supply, on selected models.
Features
- No moving parts, no obstruction and no pressure drop
- Bidirectional measurement from 0.2 to 12 m/s
- Accuracy ±0.5% of measured value; ±0.2% on request
- Repeatability ±0.2% of span
- 2-line LCD/LED display of rate and totaliser in m³, litres, gallons or ft³
- 4–20 mA standard; 0–20 mA, pulse and relay outputs optional
- RS 232 or RS 485 Modbus RTU, HART, GSM or GPRS communication options
- Transmitter IP67; flow tube IP65 standard, IP68 on remote version
- Liners from hard rubber to PTFE and PFA; electrodes from SS 316 to tantalum and platinum
Applications
- Raw water, treated water and potable water distribution
- Sewage and effluent treatment plants
- Cooling water and chilled water lines
- Acids, alkalis and chemical dosing, with a suitable liner and electrode
- Slurries in mining, pulp and paper
- Milk, juice, beer and other conductive food liquids
- Pharmaceutical process liquids
- Sugar, fertiliser, steel and aluminium plants
Specifications
Spec table.
Standard ranges and materials. Tell us your medium, range and connection and we will match the model.
| Parameter | Value |
|---|---|
| Nominal size | DN 10 to DN 2000 |
| Measuring range | 0.2 to 12 m/s, bidirectional |
| Accuracy | ±0.5% of measured value (±0.2% on request) |
| Repeatability | ±0.2% of span |
| Minimum liquid conductivity | Above 10 µS/cm |
| Working pressure | 10, 16, 25, 40 kg/cm² |
| Working temperature | Integral with PTFE liner: 120 °C; remote with PTFE liner: 180 °C; other liners: 70 °C |
| Electrode material | SS 316 standard |
| Sensor lining | Rubber standard |
| Measuring tube | SS 304 standard |
| Sensor housing | Carbon steel standard |
| End connection | Flanged, wafer or tri-clamp |
| Flange standard | ANSI 150 standard |
| Display version | Integral or remote |
| Display | 2-line LCD/LED |
| Display units | m³, litre, gallon, ft³, imperial gallon |
| Output | 4–20 mA standard |
| Power supply | 24 V DC or 80–300 V AC |
| Protection, flow tube | IP65 standard; IP68 optional on remote version |
| Protection, transmitter | IP67 |
| Remote cable length | 10 m standard |
| Installation | Inline, flanged |
Ordering options
| Parameter | Value |
|---|---|
| Option | Choices |
| Transmitter | Integral; remote |
| Power supply | 24 V DC; 80–300 V AC; solar; battery (selected models) |
| Output | 4–20 mA; 0–20 mA; pulse; relay; combinations |
| Communication | RS 232 (Modbus RTU); RS 485 (Modbus RTU); HART; GSM; GPRS |
| Data logger | External, on request |
| Pressure rating | 5 (selected models), 10, 16, 25, 40 kg/cm² |
| Sensor design | Flange ANSI 150; flange DIN PN; flange BS 10 Table D/E; wafer; SMS; tri-clamp |
| Flange material | CS/MS; SS 304; SS 316 |
| Liner | Hard rubber; neoprene; PTFE; polyurethane; PFA; HDPE |
| Electrode | SS 316; SS 316L; Hastelloy C; titanium; tantalum; platinum |
| Earthing rings | None (earth electrode); SS 316; SS 316L |
| Measuring tube | SS 304; SS 316 |
| Coil housing | CS/MS; SS 304; SS 316 |
| Sensor protection | IP65; IP67; IP68 |
| Enclosure option | Flameproof version listed as an ordering option; confirm at enquiry |
Flow range by size (0.2 m/s minimum, 12 m/s maximum)
| Parameter | Value | |
|---|---|---|
| Size (DN) | Min. flow (m³/h) | Max. flow (m³/h) |
| 10 | 0.06 | 3.38 |
| 15 | 0.13 | 7.63 |
| 20 | 0.23 | 13.56 |
| 25 | 0.35 | 21.19 |
| 32 | 0.58 | 34.91 |
| 40 | 0.90 | 54.28 |
| 50 | 1.41 | 84.82 |
| 65 | 2.39 | 143.28 |
| 80 | 3.62 | 217.08 |
| 100 | 5.65 | 339.24 |
| 125 | 8.84 | 530.16 |
| 150 | 12.72 | 763.32 |
| 200 | 22.60 | 1356.00 |
| 250 | 35.20 | 2112.00 |
| 300 | 50.89 | 3053.16 |
| 350 | 69.26 | 4155.72 |
| 400 | 90.46 | 5427.84 |
| 450 | 114.49 | 6869.64 |
| 500 | 141.35 | 8481.00 |
| 600 | 203.54 | 12212.52 |
| 700 | 277.04 | 16622.40 |
| 800 | 365.44 | 21926.40 |
| 900 | 457.98 | 27478.80 |
| 1000 | 568.16 | 34089.60 |
| 1200 | 814.18 | 48850.80 |
| 1400 | 1108.18 | 66490.80 |
| 1600 | 1447.42 | 86845.20 |
| 1800 | 1831.90 | 109914.00 |
| 2000 | 2261.60 | 135696.00 |
Installation requirements
| Parameter | Value |
|---|---|
| Requirement | Detail |
| Straight pipe | At least 5D upstream and 3D downstream, free of bends, elbows, tees and valves |
| Pipe full | Flow tube must always run full; never install in a vertical line with downward flow |
| Orientation | Electrode axis horizontal within ±15°; horizontal lines preferably with a slight upward slope in the flow direction |
| Air | Piping layout must not let air collect in the flow tube |
| Earthing | Dedicated earth, conductor 2.5 mm² or larger, not shared with heavy electrical equipment |
| Non-conductive or lined pipe | Fit earthing rings at both flanges |
| Abrasive liquids | Keep velocity below 3 m/s to protect the liner |
| Flange bolts | Tighten in a cross sequence in three passes: about 50%, 80% and 100% of rated torque |
| Surroundings | No strong magnetic fields near the flow tube; weather shade for transmitter and junction box |
Other sizes, materials and outputs on request. Flow values are as printed on the datasheet for 0.2 m/s and 12 m/s.
For consultants
Consultant spec clause.
Paste it into your technical specification or BOQ, then adjust ranges and quantities to your schedule.
1. Electromagnetic flowmeter shall be of inline type working on Faraday's principle, with no moving parts and no obstruction to flow, suitable for liquids of conductivity above 10 µS/cm. 2. Meter size shall be selected from the flow schedule (DN 10 to DN 2000) so that normal velocity lies within the measuring range, with SS 304 measuring tube, carbon steel housing and flanges to ANSI 150 (DIN PN / BS 10 Table D/E as specified). 3. Liner shall be hard rubber for water service (PTFE / PFA / polyurethane for chemical or abrasive service) and electrodes SS 316 (SS 316L / Hastelloy C / titanium / tantalum to suit the fluid). 4. Measuring range shall be 0.2 to 12 m/s bidirectional, with accuracy ±0.5% of measured value and repeatability ±0.2% of span. 5. Transmitter shall be integral (remote, with 10 m cable) with a 2-line display of flow rate and totaliser and 4–20 mA output (pulse / relay / RS 485 Modbus RTU as specified), powered from 80–300 V AC (24 V DC). 6. Pressure rating shall be 10 kg/cm² (16 / 25 / 40 kg/cm²); protection IP67 for the transmitter and IP65 for the flow tube (IP68 for remote flow tubes in pits). 7. Earthing rings shall be provided where the connecting pipe is non-conductive or lined, and the installation shall provide 5D upstream and 3D downstream straight length with the tube always full. 8. Each flowmeter shall be supplied with a manufacturer's calibration certificate, dimensional drawing and installation manual. Make: Pioneer Industrial Instruments, Pune, or approved equivalent.
What is the minimum conductivity for an electromagnetic flowmeter?
The liquid must conduct electricity for a magmeter to work, and Pioneer's installation manual specifies more than 10 µS/cm. Water, effluent, acids, alkalis, milk and most slurries are well above this. Oils, hydrocarbons, solvents and demineralised water are not, so use a vortex, turbine, ultrasonic or mass flowmeter for those.
How much straight pipe does a magmeter need?
Provide at least five pipe diameters (5D) of straight pipe upstream and three diameters (3D) downstream, free of bends, tees and valves. Mount the meter where the tube stays full: in a horizontal line with a slight upward slope, or a vertical line with upward flow. Never install it in a downward vertical line or at a high point where air collects.
How do I size an electromagnetic flowmeter?
Size on velocity, not just on line size. The meter covers 0.2 to 12 m/s; for good accuracy and liner life, aim for roughly 1 to 3 m/s at normal flow and keep abrasive slurries below 3 m/s. A DN 100 meter, for example, covers 5.65 to 339 m³/h. If normal velocity is very low, a smaller meter with reducers often reads better.
Which liner and electrode should I choose?
For water and effluent, a hard rubber or neoprene liner with SS 316 electrodes is the usual choice. Use PTFE or PFA for acids, alkalis and hot liquids (PTFE to 120 °C integral, 180 °C remote), polyurethane for abrasive slurries and HDPE for low-pressure water. For aggressive chemicals, choose SS 316L, Hastelloy C, titanium, tantalum or platinum electrodes after checking compatibility with every component of the fluid.
Why does a magmeter need earthing rings?
The meter measures a very small voltage referenced to the liquid. In bare metal pipes, the pipe provides this reference. In plastic, FRP or internally lined pipes, fit earthing rings on both flanges and bond them to the meter. Use a dedicated earth conductor of at least 2.5 mm² and do not share it with heavy electrical equipment, or the reading will drift and fluctuate.