Electromagnetic Flowmeters — Magmeters for Conductive Liquids

An electromagnetic flowmeter (magmeter) measures the flow of electrically conductive liquids with no moving parts and no pressure drop. Pioneer supplies inline magmeters from DN 10 to DN 2000 with accuracy of ±0.5% of measured value (±0.2% on request), for velocities of 0.2 to 12 m/s in either direction.

  • Measuring range: 0.2 to 12 m/s, bidirectional
  • Nominal size: DN 10 to DN 2000
  • Accuracy: ±0.5% of measured value (±0.2% on request)

Quotation typically within 48 hoursSupply India and export

Pioneer flanged electromagnetic flowmeter with integral display transmitter

Overview

What it does and where it fits.

A magmeter works on Faraday's law. Coils around the flow tube create a magnetic field, and a conductive liquid moving through it generates a voltage proportional to its velocity, which two electrodes pick up. Because the field strength and electrode spacing are fixed, the signal depends only on velocity, so viscosity, density and temperature changes do not affect the reading.

The liquid must conduct electricity: the installation manual calls for more than 10 µS/cm. That covers potable water, raw water, sewage, cooling water, most acids, alkalis and slurries, but not oils, hydrocarbons, solvents, demineralised water or gases. For those, use a vortex, turbine, ultrasonic or mass flowmeter.

Each meter is configured to order: integral or remote transmitter, liner, electrode, end connection and pressure rating. The tables below list the ordering options, the minimum and maximum flow for every size at 0.2 and 12 m/s, and the installation rules a site team must follow.

Types

  • Integral typeTransmitter mounted on the flow tube, for accessible locations where one compact unit is preferred.
  • Remote typeFlow tube with junction box and a separate wall- or pipe-mounted transmitter, connected by a 10 m standard cable; allows an IP68 flow tube for pits and flood-prone chambers.
  • Flanged, wafer and sanitary endsFlanges to ANSI 150, DIN PN or BS 10 Table D/E, wafer pattern, or SMS and tri-clamp ends for food and pharmaceutical lines.
  • Solar or battery poweredListed ordering options for remote water lines without a mains supply, on selected models.

Features

  • No moving parts, no obstruction and no pressure drop
  • Bidirectional measurement from 0.2 to 12 m/s
  • Accuracy ±0.5% of measured value; ±0.2% on request
  • Repeatability ±0.2% of span
  • 2-line LCD/LED display of rate and totaliser in m³, litres, gallons or ft³
  • 4–20 mA standard; 0–20 mA, pulse and relay outputs optional
  • RS 232 or RS 485 Modbus RTU, HART, GSM or GPRS communication options
  • Transmitter IP67; flow tube IP65 standard, IP68 on remote version
  • Liners from hard rubber to PTFE and PFA; electrodes from SS 316 to tantalum and platinum

Applications

  • Raw water, treated water and potable water distribution
  • Sewage and effluent treatment plants
  • Cooling water and chilled water lines
  • Acids, alkalis and chemical dosing, with a suitable liner and electrode
  • Slurries in mining, pulp and paper
  • Milk, juice, beer and other conductive food liquids
  • Pharmaceutical process liquids
  • Sugar, fertiliser, steel and aluminium plants

Specifications

Spec table.

Standard ranges and materials. Tell us your medium, range and connection and we will match the model.

ParameterValue
Nominal sizeDN 10 to DN 2000
Measuring range0.2 to 12 m/s, bidirectional
Accuracy±0.5% of measured value (±0.2% on request)
Repeatability±0.2% of span
Minimum liquid conductivityAbove 10 µS/cm
Working pressure10, 16, 25, 40 kg/cm²
Working temperatureIntegral with PTFE liner: 120 °C; remote with PTFE liner: 180 °C; other liners: 70 °C
Electrode materialSS 316 standard
Sensor liningRubber standard
Measuring tubeSS 304 standard
Sensor housingCarbon steel standard
End connectionFlanged, wafer or tri-clamp
Flange standardANSI 150 standard
Display versionIntegral or remote
Display2-line LCD/LED
Display unitsm³, litre, gallon, ft³, imperial gallon
Output4–20 mA standard
Power supply24 V DC or 80–300 V AC
Protection, flow tubeIP65 standard; IP68 optional on remote version
Protection, transmitterIP67
Remote cable length10 m standard
InstallationInline, flanged

Ordering options

ParameterValue
OptionChoices
TransmitterIntegral; remote
Power supply24 V DC; 80–300 V AC; solar; battery (selected models)
Output4–20 mA; 0–20 mA; pulse; relay; combinations
CommunicationRS 232 (Modbus RTU); RS 485 (Modbus RTU); HART; GSM; GPRS
Data loggerExternal, on request
Pressure rating5 (selected models), 10, 16, 25, 40 kg/cm²
Sensor designFlange ANSI 150; flange DIN PN; flange BS 10 Table D/E; wafer; SMS; tri-clamp
Flange materialCS/MS; SS 304; SS 316
LinerHard rubber; neoprene; PTFE; polyurethane; PFA; HDPE
ElectrodeSS 316; SS 316L; Hastelloy C; titanium; tantalum; platinum
Earthing ringsNone (earth electrode); SS 316; SS 316L
Measuring tubeSS 304; SS 316
Coil housingCS/MS; SS 304; SS 316
Sensor protectionIP65; IP67; IP68
Enclosure optionFlameproof version listed as an ordering option; confirm at enquiry

Flow range by size (0.2 m/s minimum, 12 m/s maximum)

ParameterValue
Size (DN)Min. flow (m³/h)Max. flow (m³/h)
100.063.38
150.137.63
200.2313.56
250.3521.19
320.5834.91
400.9054.28
501.4184.82
652.39143.28
803.62217.08
1005.65339.24
1258.84530.16
15012.72763.32
20022.601356.00
25035.202112.00
30050.893053.16
35069.264155.72
40090.465427.84
450114.496869.64
500141.358481.00
600203.5412212.52
700277.0416622.40
800365.4421926.40
900457.9827478.80
1000568.1634089.60
1200814.1848850.80
14001108.1866490.80
16001447.4286845.20
18001831.90109914.00
20002261.60135696.00

Installation requirements

ParameterValue
RequirementDetail
Straight pipeAt least 5D upstream and 3D downstream, free of bends, elbows, tees and valves
Pipe fullFlow tube must always run full; never install in a vertical line with downward flow
OrientationElectrode axis horizontal within ±15°; horizontal lines preferably with a slight upward slope in the flow direction
AirPiping layout must not let air collect in the flow tube
EarthingDedicated earth, conductor 2.5 mm² or larger, not shared with heavy electrical equipment
Non-conductive or lined pipeFit earthing rings at both flanges
Abrasive liquidsKeep velocity below 3 m/s to protect the liner
Flange boltsTighten in a cross sequence in three passes: about 50%, 80% and 100% of rated torque
SurroundingsNo strong magnetic fields near the flow tube; weather shade for transmitter and junction box

Other sizes, materials and outputs on request. Flow values are as printed on the datasheet for 0.2 m/s and 12 m/s.

For consultants

Consultant spec clause.

Paste it into your technical specification or BOQ, then adjust ranges and quantities to your schedule.

electromagnetic-flowmeters · spec clause
1. Electromagnetic flowmeter shall be of inline type working on Faraday's principle, with no moving parts and no obstruction to flow, suitable for liquids of conductivity above 10 µS/cm.
2. Meter size shall be selected from the flow schedule (DN 10 to DN 2000) so that normal velocity lies within the measuring range, with SS 304 measuring tube, carbon steel housing and flanges to ANSI 150 (DIN PN / BS 10 Table D/E as specified).
3. Liner shall be hard rubber for water service (PTFE / PFA / polyurethane for chemical or abrasive service) and electrodes SS 316 (SS 316L / Hastelloy C / titanium / tantalum to suit the fluid).
4. Measuring range shall be 0.2 to 12 m/s bidirectional, with accuracy ±0.5% of measured value and repeatability ±0.2% of span.
5. Transmitter shall be integral (remote, with 10 m cable) with a 2-line display of flow rate and totaliser and 4–20 mA output (pulse / relay / RS 485 Modbus RTU as specified), powered from 80–300 V AC (24 V DC).
6. Pressure rating shall be 10 kg/cm² (16 / 25 / 40 kg/cm²); protection IP67 for the transmitter and IP65 for the flow tube (IP68 for remote flow tubes in pits).
7. Earthing rings shall be provided where the connecting pipe is non-conductive or lined, and the installation shall provide 5D upstream and 3D downstream straight length with the tube always full.
8. Each flowmeter shall be supplied with a manufacturer's calibration certificate, dimensional drawing and installation manual.
Make: Pioneer Industrial Instruments, Pune, or approved equivalent.

FAQ

Questions about Electromagnetic Flowmeter.

Anything else? Call or WhatsApp +91 93700 39974.

What is the minimum conductivity for an electromagnetic flowmeter?

The liquid must conduct electricity for a magmeter to work, and Pioneer's installation manual specifies more than 10 µS/cm. Water, effluent, acids, alkalis, milk and most slurries are well above this. Oils, hydrocarbons, solvents and demineralised water are not, so use a vortex, turbine, ultrasonic or mass flowmeter for those.

How much straight pipe does a magmeter need?

Provide at least five pipe diameters (5D) of straight pipe upstream and three diameters (3D) downstream, free of bends, tees and valves. Mount the meter where the tube stays full: in a horizontal line with a slight upward slope, or a vertical line with upward flow. Never install it in a downward vertical line or at a high point where air collects.

How do I size an electromagnetic flowmeter?

Size on velocity, not just on line size. The meter covers 0.2 to 12 m/s; for good accuracy and liner life, aim for roughly 1 to 3 m/s at normal flow and keep abrasive slurries below 3 m/s. A DN 100 meter, for example, covers 5.65 to 339 m³/h. If normal velocity is very low, a smaller meter with reducers often reads better.

Which liner and electrode should I choose?

For water and effluent, a hard rubber or neoprene liner with SS 316 electrodes is the usual choice. Use PTFE or PFA for acids, alkalis and hot liquids (PTFE to 120 °C integral, 180 °C remote), polyurethane for abrasive slurries and HDPE for low-pressure water. For aggressive chemicals, choose SS 316L, Hastelloy C, titanium, tantalum or platinum electrodes after checking compatibility with every component of the fluid.

Why does a magmeter need earthing rings?

The meter measures a very small voltage referenced to the liquid. In bare metal pipes, the pipe provides this reference. In plastic, FRP or internally lined pipes, fit earthing rings on both flanges and bond them to the meter. Use a dedicated earth conductor of at least 2.5 mm² and do not share it with heavy electrical equipment, or the reading will drift and fluctuate.