Indoor Air Quality (IAQ) Sensors — CO2, Temperature, Humidity and Particulate Monitoring
Pioneer supplies indoor air quality (IAQ) sensors that measure CO2, temperature and humidity, with VOC, PM2.5/PM10, ozone and formaldehyde available by model, for BMS monitoring and ventilation control. Fixed temperature and humidity transmitters give 4–20 mA, 0–10 V DC or RS485 output, and a portable CO2 monitor covers 400–5,000 ppm.
- Output (transmitters): 4–20 mA, 0–10 V DC, RS485

Overview
What it does and where it fits.
IAQ sensors tell the building management system whether a space is ventilated, filtered and conditioned well enough for the people in it. CO2 shows ventilation against occupancy, temperature and humidity show thermal comfort and mould risk, and VOC, formaldehyde and particulate readings show pollutants from materials, cleaning products and outdoor air.
Pick the parameters to match the decision the reading will drive. CO2 alone is enough for demand-controlled ventilation. Add PM2.5 where filtration performance matters, such as near traffic or in hospitals, and VOC or formaldehyde for new fit-outs and green building IAQ credits.
Pioneer supplies temperature and humidity transmitters with analogue and RS485 outputs, multi-parameter room IAQ sensors, and a battery-powered portable monitor that reads CO2, temperature and humidity for surveys and commissioning checks.
Types
- Multi-parameter room IAQ sensorWall-mounted sensor combining CO2 with temperature and humidity, and VOC, PM2.5/PM10, ozone or formaldehyde where required.
- Temperature and humidity transmitterCompact transmitter with probe and M16 cable entry, giving 4–20 mA, 0–10 V DC or RS485 output to the BMS.
- Portable CO2, temperature and humidity monitorRechargeable handheld monitor with backlit LCD for IAQ surveys, ventilation audits and commissioning.
Features
- CO2, temperature and humidity as the core parameters
- VOC, PM2.5/PM10, ozone and formaldehyde available by model
- 4–20 mA, 0–10 V DC or RS485 output on transmitters
- 0.1 °C and 0.1 %RH resolution on T/RH transmitters
- Portable monitor with backlit LCD and USB Type-C charging
Applications
- Offices, schools and retail spaces
- Hospitals and clinics
- Demand-controlled ventilation through the BMS
- Green building IAQ monitoring (LEED, IGBC, GRIHA)
- Smart building dashboards
- Industrial hygiene and workplace air checks
- IAQ surveys and HVAC commissioning
Specifications
Spec table.
Standard ranges and materials. Tell us your medium, range and connection and we will match the model.
| Parameter | Value |
|---|---|
| Parameters (select by model) | CO2, temperature, relative humidity, VOC, PM2.5, PM10, CO, ozone, formaldehyde |
| Output (transmitters) | 4–20 mA, 0–10 V DC, RS485 |
Temperature and humidity transmitter
| Parameter | Value |
|---|---|
| Resolution | Temperature 0.1 °C, humidity 0.1 %RH |
| Output | 4–20 mA, 0–10 V DC, RS485 |
| Power consumption | 60 mA |
| Case size | 80 x 65 x 38 mm |
| Probe size | 42 x 16 mm |
| Cable entry | M16 x 1.5 mm |
Portable CO2, temperature and humidity monitor
| Parameter | Value |
|---|---|
| CO2 range | 400–5,000 ppm |
| CO2 sensitivity | 1 ppm |
| Temperature range / accuracy | 0–50 °C / ±1 °C |
| Humidity range / accuracy | 0–99 %RH / ±5 %RH |
| Display | LCD with backlight |
| Battery | 1200 mAh, USB Type-C charging |
Range and accuracy for VOC, particulate, ozone and formaldehyde sensing are confirmed per model at enquiry.
For consultants
Consultant spec clause.
Paste it into your technical specification or BOQ, then adjust ranges and quantities to your schedule.
1. Indoor air quality sensors shall be provided in the spaces shown on the drawings to measure CO2, temperature and relative humidity [plus PM2.5/PM10 and TVOC where scheduled]. 2. CO2 shall be measured by a non-dispersive infrared (NDIR) element over the scheduled range (typically 400–2,000 ppm). 3. Temperature and humidity shall be displayed and transmitted with a resolution of 0.1 °C and 0.1 %RH. 4. Output shall be RS485 (Modbus RTU) [or 4–20 mA / 0–10 V DC per parameter] for connection to the BMS. 5. Sensors shall be wall mounted at 1.2–1.5 m above finished floor in the occupied zone, away from doors, windows, supply diffusers and heat sources. 6. Each sensor shall be supplied with a manufacturer's test/calibration certificate, wiring diagram and Modbus register map. Make: Pioneer Industrial Instruments, Pune, or approved equivalent.
Which parameters should an IAQ sensor measure for an office?
For most offices, CO2, temperature and relative humidity are enough: CO2 drives demand-controlled ventilation and the other two cover comfort. Add PM2.5 if the building is near heavy traffic or the AHU filtration needs to be verified, and TVOC or formaldehyde for new fit-outs or green building IAQ credits. Each extra parameter adds cost and maintenance, so specify only the ones the BMS will act on.
Should I choose an analogue or RS485 output for BMS integration?
RS485 with Modbus RTU carries all parameters from a multi-parameter sensor on one two-wire bus, which saves cabling and BMS input points. Analogue 4–20 mA or 0–10 V gives one signal per parameter and suits simple single-parameter loops or controllers without a Modbus port. Pioneer's temperature and humidity transmitters offer 4–20 mA, 0–10 V DC and RS485.
Where should a room IAQ sensor be installed?
Mount it in the occupied zone, typically 1.2–1.5 m above the floor, on an internal wall with free air movement. Keep it away from doors, windows, supply diffusers, printers, kitchens and direct sunlight, which give readings that do not represent the room. In large open offices, use one sensor per ventilation zone so the BMS can act on each zone separately.
How accurate are low-cost particulate and VOC sensors?
Optical PM sensors and metal-oxide VOC sensors are good at showing trends and relative changes, but they are not reference instruments. PM readings can be affected by humidity, and TVOC readings depend on which compounds are present. Use them to trigger ventilation or filter checks, not as compliance measurements. CO2 sensors using NDIR are the most stable of the common IAQ parameters.